Power Factor Calculator

Power factor from any two of kW, kVA and kVAR, with the phase angle, the line current at your voltage and the capacitor kVAR to reach a target. How it works

Use the Power Factor Calculator

Known values

For capacitor sizing. Leave blank to skip.

For the line current. Line to line for three phase. Needs kW and kVA, not other units.

Supply type
Power factor
0.800
Reactive power 75.00 · Phase angle 36.87°

Phase angle θ = acos(PF)
36.87° / 0.6435 rad

PF = kW ÷ kVA and kVAR = √(kVA² − kW²); with any two of kW, kVAR and kVA known, the third follows from kVA² = kW² + kVAR². The units are only labels: use the same prefix (W, kW or MW) in both fields. The line current is the exception: it assumes the apparent power is in kVA (and the real power in kW), so enter kW and kVA when you give a voltage.

Whether the load is lagging (inductive) or leading (capacitive) cannot be told from these two numbers, so it is not reported. A negative real power means power flowing back to the source and gives a negative power factor.

The capacitor figure assumes an inductive load and is the reactive power to cancel, not a product selection: real installations also account for voltage, harmonics and the capacitor rating.

About the Power Factor Calculator

Power factor is real power divided by apparent power: 100 kW drawn as 125 kVA is a power factor of 0.800, with 75.00 kVAR of reactive power and a phase angle of 36.87°. This power factor calculator also sizes the capacitor for a target power factor: 42.13 kVAR takes that 100 kW load from 0.800 to 0.95. It accepts any two of kW, kVA and kVAR, and gives the line current when you type the supply voltage.

Power factor, reactive power and phase angle

Real power (kW)Apparent power (kVA)Power factorReactive power (kVAR)Phase angle
1001250.80075.0036.87° / 0.6435 rad
801000.80060.0036.87° / 0.6435 rad
951000.95031.2218.19° / 0.3176 rad
901000.90043.5925.84° / 0.4510 rad
701000.70071.4145.57° / 0.7954 rad
501000.50086.6060.00° / 1.0472 rad
1001001.0000.000.00° / 0.0000 rad
01000.000100.0090.00° / 1.5708 rad
-4050-0.80030.00143.13° / 2.4981 rad

The page prints reactive power without a unit because it is in the unit of your inputs: kW and kVA give kVAR, W and VA give VAR.

Capacitor kVAR to reach a target power factor

Real power (kW)Apparent power (kVA)Present power factorTargetCapacitor (kVAR)
1001250.8000.9026.57
1001250.8000.9542.13
1001250.8000.9854.69
1001250.800175.00
701000.7000.9037.51
701000.7000.9548.41
901000.9000.85None needed: already at or above the target

Qc = kW × (tan θ1 − tan θ2), for an inductive load. The figure is the reactive power to cancel, in the unit of your inputs; a real capacitor bank is chosen from standard ratings for the supply voltage.

Frequently asked questions

How do you calculate power factor from kW and kVA?
Divide kW by kVA. 90 kW at 100 kVA is a power factor of 0.900; the reactive power is √(100² − 90²) = 43.59 kVAR and the phase angle acos(0.9) = 25.84°.
How do I size a capacitor for power factor correction?
Qc = kW × (tan θ1 − tan θ2), with θ1 = acos(present PF) and θ2 = acos(target PF). For 100 kW at 0.800 corrected to 0.95: 100 × (0.75 − 0.3287) = 42.13 kVAR. Enter the target in the optional field to get this figure.
Can it tell whether the power factor is leading or lagging?
No. kW and kVA give the size of the reactive power, not its sign, so the calculator does not report lagging (inductive) or leading (capacitive). The capacitor figure assumes an inductive load, the common case for motors.
What does a negative power factor mean?
A negative real power means power flowing back to the source, for example from a generator or solar inverter. -40 kW at 50 kVA gives -0.800 and a phase angle of 143.13°.
Why does it refuse kW larger than kVA?
Apparent power is the hypotenuse of the power triangle, kVA² = kW² + kVAR², so real power cannot exceed it. 130 kW with 125 kVA is refused instead of showing a power factor above 1.
How do I convert between kVA and amps?
Type the supply voltage and pick the phase, and the page gives the line current from the apparent power: I = kVA × 1,000 ÷ V for single phase, I = kVA × 1,000 ÷ (√3 × V) for three phase with V line to line. 125 kVA at 400 V three phase is 180.42 A; at 230 V single phase it is 543.48 A. The other way, kVA = √3 × volts × amps ÷ 1,000, so 480 V at 120 A three phase is 99.77 kVA; type that in as kVA yourself.