Reynolds Number
Reynolds number Re = ρvL/μ, or vL/ν from kinematic viscosity, in SI units with water and air presets, labeled laminar, transitional or turbulent for pipe flow. How it works
Use the Reynolds Number
About the Reynolds Number
Water at 20 °C moving at 0.1 m/s through a 50 mm pipe has a Reynolds number of 4,983.08, just above the turbulent limit of 4,000. Re = ρvL ÷ μ: density times velocity times pipe diameter, divided by dynamic viscosity. This Reynolds number calculator labels the result laminar below 2,300, transitional from 2,300 to 4,000 and turbulent above 4,000, the usual limits for flow in a pipe.
Reynolds numbers for water and air
| Fluid | Density (kg/m³) | Viscosity (Pa·s) | Velocity (m/s) | Length (m) | Re | Pipe-flow label |
|---|---|---|---|---|---|---|
| Water, 20 °C | 998.21 | 0.0010016 | 0.02 | 0.05 | 996.615 | Laminar |
| Water, 20 °C | 998.21 | 0.0010016 | 0.046 | 0.05 | 2,292.22 | Laminar |
| Water, 20 °C | 998.21 | 0.0010016 | 0.05 | 0.05 | 2,491.54 | Transitional |
| Water, 20 °C | 998.21 | 0.0010016 | 0.08 | 0.05 | 3,986.46 | Transitional |
| Water, 20 °C | 998.21 | 0.0010016 | 0.1 | 0.05 | 4,983.08 | Turbulent |
| Water, 20 °C | 998.21 | 0.0010016 | 1 | 0.05 | 49,830.8 | Turbulent |
| Water, 20 °C | 998.21 | 0.0010016 | 1 | 0.1 | 99,661.5 | Turbulent |
| Water, 10 °C | 999.70 | 0.0013060 | 0.1 | 0.05 | 3,827.34 | Transitional |
| Water, 60 °C | 983.20 | 0.0004660 | 0.1 | 0.05 | 10,549.4 | Turbulent |
| Air, 20 °C, 1 atm | 1.204 | 0.00001813 | 0.5 | 0.01 | 332.046 | Laminar |
| Air, 20 °C, 1 atm | 1.204 | 0.00001813 | 2 | 0.05 | 6,640.93 | Turbulent |
| Air, 20 °C, 1 atm | 1.204 | 0.00001813 | 10 | 0.1 | 66,409.3 | Turbulent |
| Air, 20 °C, 1 atm | 1.204 | 0.00001813 | 30 | 1 | 1,992,280 | Turbulent |
Fluid properties from The Engineering ToolBox tables: water density 999.70, 998.21 and 983.20 kg/m³ and viscosity 0.0013060, 0.0010016 and 0.0004660 Pa·s at 10, 20 and 60 °C; air at 20 °C and 1 atm 1.204 kg/m³ and 18.13 µPa·s. The tool’s own fluid presets use slightly different handbook figures (water at 20 °C 0.001002 Pa·s, air 0.00001825 Pa·s), so with a preset the 0.1 m/s water row gives 4,981.09. The label assumes flow inside a full circular pipe with L as its diameter.
Frequently asked questions
- What Reynolds number is laminar flow?
- In a full circular pipe, flow is laminar below about 2,300 and turbulent above 4,000 by the usual engineering limits; in between it can switch back and forth. Those limits are a convention: Wikipedia’s article gives turbulent flow from about 2,900 for fully developed pipe flow. The calculator labels by 2,300 and 4,000.
- What is the Reynolds number of air?
- It depends on speed and size. With air at 20 °C (1.204 kg/m³, 0.00001813 Pa·s), 10 m/s over 0.1 m gives 66,409.3, while 0.5 m/s in a 10 mm tube gives 332.046.
- Does water temperature change the Reynolds number?
- Yes, mainly through viscosity, which falls as water warms. In a 50 mm pipe at 0.1 m/s, Re is 3,827.34 at 10 °C (transitional), 4,983.08 at 20 °C and 10,549.4 at 60 °C (both turbulent).
- Do the 2,300 and 4,000 limits apply to a plate, a hull or a river?
- No. The critical Reynolds number is different for every geometry; a boundary layer on a flat plate turns turbulent near 500,000, measured from the leading edge. Use the number for those cases, but not the pipe-flow label.
- What units does it use?
- SI only: density in kg/m³, velocity in m/s, length in m and dynamic viscosity in Pa·s, or kinematic viscosity in m²/s. Viscosity in centipoise divides by 1,000 (1 cP = 0.001 Pa·s), and centistokes by 1,000,000 to give m²/s. For a non-circular duct, enter the hydraulic diameter as the length. Every value must be above 0.
- Can I use kinematic viscosity instead?
- Yes. Set Viscosity given as to kinematic and Re = v × L ÷ ν, with no density field. Switching converts the typed value with ν = μ ÷ ρ. With ν = 0.000001 m²/s (about water at 20 °C), 1 m/s in a 50 mm pipe gives 50,000. The presets fill both forms: air at 20 °C is 0.000015158 m²/s.
Related Tools
View all toolsMolar Mass Calculator
Molar mass of a chemical formula in g/mol from IUPAC atomic weights, with each element’s mass percent. Reads brackets and hydrates such as CuSO4·5H2O.
Kinetic Energy Calculator
Kinetic energy from mass and speed by KE = ½mv², or mass or speed from the energy, in metric or US units, with the result also in kWh, kcal and BTU.
Power Factor Calculator
Power factor from any two of kW, kVA and kVAR, with the phase angle, the line current at your voltage and the capacitor kVAR to reach a target.
Pressure Drop Calculator
Pipe pressure drop for water, air or a custom fluid by Darcy-Weisbach, or Hazen-Williams for water, in gpm, inches and psi or metric units.
Solar Panel Output Calculator
Solar panel output in kWh per day, month and year from peak sun hours, roof area or a panel count, panel watts, losses and tilt, plus CO₂ offset.
Specific Heat Calculator
Heat to warm or cool a mass of 16 preset materials, from water to copper, or your own specific heat: Q = m × c × ΔT, in J, kJ, MJ or BTU.