Server Rack Power Budget

Add up server and device watts to get the rack load in kW, its heat in BTU per hour, a branch circuit size and the monthly and yearly energy cost. How it works

Use the Server Rack Power Budget

1 means watts equal VA. Take it from the PSU datasheet.

Redundant PSU configuration

N+1: one spare PSU per server, so a server still carries its full load after one PSU fails. Power draw is unchanged.

Total Power Draw
5.10 kW
BTU/hr 17,401 · Monthly $446.76

Power

5.00 kW servers + 100 W additional

Annual Cost

$5,361.12

Current at 208 V

2.40 A per server, 0.24 A per other device, 24.5 A total

Apparent power 5.10 kVA for 5.10 kW at power factor 1. To convert between kW, kVA and kvar, use the power factor calculator.

Circuit size

50A 208V circuit recommended (8,320 W continuous of its 10,400 W rating)

PSUs to provision

2 × 1000 W per server

1 needed to carry the load, 1 spare. Rack total: 20 PSUs, 20.00 kW installed capacity; each PSU carries 25% of its rating while all are present.

Normal power draw

Formula Reference

Total Power: Servers × Watts + Additional Devices × Watts (redundancy does not change the draw)

PSUs per server: ceil(Watts ÷ PSU rating) needed + spares (0, 1 or 2)

Current: Watts ÷ power factor ÷ supply voltage (single-phase; the circuit is sized on watts ÷ power factor, in VA)

BTU/hr: Total Power (W) × 3.412

Monthly Cost: (Total Power / 1000) × Cost per kWh × Hours

Annual Cost: Monthly Cost × 12

About the Server Rack Power Budget

Ten servers drawing 500 W each plus two 50 W switches make a 5.10 kW rack, which gives off 17,401 BTU/hr of heat and costs $446.76 a month at $0.12 per kWh around the clock. The rack power calculator adds the watts, converts them to BTU per hour (W × 3.412), prices the energy and suggests a 208 V branch circuit sized by the 80% continuous-load rule: 5.10 kW is over the 4,992 W a 30 A circuit carries, so it needs 50 A.

Rack load, heat, cost and circuit (two 50 W devices, $0.12 per kWh, 730 h)

ServersTotal loadHeatEnergy cost a monthCircuit suggested
4 at 350 W1.50 kW5,118 BTU/hr$131.4030 A, 208 V
8 at 600 W4.90 kW16,719 BTU/hr$429.2430 A, 208 V
10 at 500 W5.10 kW17,401 BTU/hr$446.7650 A, 208 V
16 at 400 W6.50 kW22,178 BTU/hr$569.4050 A, 208 V
20 at 450 W9.10 kW31,049 BTU/hr$797.1655 A or more, 208 V

Above 8,320 W, the continuous limit of a 50 A circuit, the tool states the amps needed and says to contact facility power.

How to use this tool

  1. Enter the number of servers and the watts each one actually draws, from a power meter, the PDU readout or the vendor’s typical-load figure.
  2. Add other devices such as switches and storage with their watts, then the PSU rating and the redundancy (N, N+1 or N+2).
  3. Enter your price per kWh and the hours per month (730 is a full month). The totals update as you type.
  4. Set the supply voltage (120, 208 or 240 V single-phase, or your own) and the power factor from the PSU datasheet. The page shows the current per server, per other device and in total, and sizes the circuit on VA.

Frequently asked questions

How do you convert watts to BTU per hour?
Multiply by 3.412. A 5,100 W rack gives off 17,401 BTU/hr, which is about 1.45 tons of cooling at 12,000 BTU/hr per ton. Every watt a server draws ends up as heat in the room.
Should I enter the PSU rating or the measured watts?
The measured or typical draw. A power supply’s rating is the most it can deliver, not what the server takes from the wall. Entering nameplate ratings as the draw overstates the heat, the cost and the circuit size.
What size circuit does a server rack need?
A breaker must be rated at least 125% of a continuous load, so a load may use 80% of the breaker. At 208 V that is 4,992 W on a 30 A circuit and 8,320 W on a 50 A circuit. The tool sizes the circuit on VA (watts ÷ power factor) at the single-phase voltage you set: the default 5.10 kW draws 24.5 A at 208 V and needs 50 A, while at 240 V a 30 A circuit carries 5,760 W and is enough. Three-phase feeds are not modeled.
What does N+1 mean for power supplies?
Enough PSUs to carry the server, plus one spare. An 1,800 W server on 1,000 W supplies needs 2, so N+1 means 3, and with all three running each carries 60% of its rating. Redundancy changes the PSU count, not the power the rack draws.
Does the energy cost include cooling?
No. It prices only the IT load you entered, at a constant draw for the hours given. The cooling plant and power losses in UPS and distribution add to the real bill.