Voltage Drop Calculator
Voltage drop in volts and percent for copper or aluminum wire, 22 AWG to 1000 kcmil, DC, single- or three-phase, from one-way feet, amps and source volts. How it works
Use the Voltage Drop Calculator
About the Voltage Drop Calculator
12 AWG copper carrying 10 A for 100 ft one way on 120 V drops 3.95 V, 3.29% of the source, which is above the 3% the NEC recommends for a branch circuit; 10 AWG drops 2.49 V (2.07%). Voltage drop = 2 × K × L × I ÷ A for DC or single-phase, and √3 in place of the 2 for three-phase, with K = 12.9 for copper or 21.2 for aluminum, L the one-way length in feet and A the wire area in circular mils.
Voltage drop on a 120 V copper circuit, 100 ft one way
| Wire | 10 A | 15 A | 20 A | 30 A |
|---|---|---|---|---|
| 14 AWG | 6.28 V (5.23%) | 9.42 V (7.85%) | 12.55 V (10.46%) | 18.83 V (15.69%) |
| 12 AWG | 3.95 V (3.29%) | 5.93 V (4.94%) | 7.90 V (6.58%) | 11.85 V (9.88%) |
| 10 AWG | 2.49 V (2.07%) | 3.73 V (3.11%) | 4.97 V (4.14%) | 7.46 V (6.21%) |
| 8 AWG | 1.56 V (1.30%) | 2.34 V (1.95%) | 3.13 V (2.60%) | 4.69 V (3.91%) |
| 6 AWG | 0.98 V (0.82%) | 1.47 V (1.23%) | 1.97 V (1.64%) | 2.95 V (2.46%) |
DC or single-phase, K = 12.9 at 75 °C. At 240 V the volts dropped are the same and the percentage is half. These are voltage-drop figures, not current ratings.
Smallest copper wire that keeps the drop within 3% at 120 V
| One-way length | 10 A | 15 A | 20 A | 30 A |
|---|---|---|---|---|
| 25 ft | 16 AWG | 14 AWG | 14 AWG | 12 AWG |
| 50 ft | 14 AWG | 12 AWG | 10 AWG | 8 AWG |
| 75 ft | 12 AWG | 10 AWG | 8 AWG | 8 AWG |
| 100 ft | 10 AWG | 8 AWG | 8 AWG | 6 AWG |
| 150 ft | 8 AWG | 8 AWG | 6 AWG | 4 AWG |
| 200 ft | 8 AWG | 6 AWG | 4 AWG | 3 AWG |
Single-phase, from the sizes the calculator lists (22 AWG to 1000 kcmil), judged on the percentage as shown to two decimals. The current rating of the wire, its insulation and the terminals can call for a larger size; this table does not check them.
Smallest copper wire that keeps a 12 V DC drop within 3%
| One-way length | 5 A | 10 A | 20 A | 30 A |
|---|---|---|---|---|
| 5 ft | 16 AWG | 14 AWG | 10 AWG | 8 AWG |
| 10 ft | 14 AWG | 10 AWG | 8 AWG | 6 AWG |
| 15 ft | 12 AWG | 8 AWG | 6 AWG | 4 AWG |
| 20 ft | 10 AWG | 8 AWG | 4 AWG | 3 AWG |
| 25 ft | 10 AWG | 6 AWG | 4 AWG | 2 AWG |
A 3% drop at 12 V is 0.36 V. The length is from the battery to the load; the formula counts the return wire. Current ratings are not checked.
Smallest copper wire for 10 A within 3% at 12, 24 and 48 V DC
| One-way length | 12 V | 24 V | 48 V |
|---|---|---|---|
| 5 ft | 14 AWG | 16 AWG | 20 AWG |
| 10 ft | 10 AWG | 14 AWG | 16 AWG |
| 25 ft | 6 AWG | 10 AWG | 12 AWG |
| 50 ft | 4 AWG | 6 AWG | 10 AWG |
The same current loses the same volts at any system voltage, so doubling the voltage halves the percentage and allows a thinner wire. At 1 A and 12 V the smallest size within 3% is 22 AWG at 5 ft one way, 20 AWG at 10 ft and 18 AWG at 20 ft. Current ratings are not checked.
How to use this tool
- Pick the material, the wire size (22 AWG to 1000 kcmil, or 0.5 to 500 mm²) and the circuit: DC or single-phase, or three-phase line to line.
- Enter the one-way length from the source to the load in feet, the load current in amps and the source voltage, or tap a preset: 12, 24, 48, 120 or 240 V.
- Pick the drop limit (1, 2, 3 or 5%). The drop, the longest run the chosen wire carries within the limit, the smallest listed wire within it and the drop on every size update as you type.
- A link can fill the form: voltage, amps, length, gauge (0 to 0000 also read as 1/0 to 4/0, or a metric size such as 2.5mm2), material, circuit and maxdrop, as in ?voltage=24&s=10&length=25&gauge=10.
Frequently asked questions
- What is the voltage drop on 12 gauge wire at 100 feet?
- On copper at 120 V, 3.95 V (3.29%) at 10 A and 7.90 V (6.58%) at 20 A, which leaves 112.10 V at the load. 10 AWG at 20 A drops 4.97 V (4.14%). The 100 ft is one way; the formula already counts the return conductor.
- Is the length one way or round trip?
- One way, from the source to the load. The formula doubles it for the go and return conductors. Entering the round-trip 200 ft for a 100 ft run of 12 AWG at 10 A and 120 V gives 7.90 V instead of 3.95 V.
- What voltage drop does the NEC allow?
- Informational notes to NEC 210.19 (branch circuits) and 215.2 (feeders) recommend sizing conductors for no more than 3% drop on the branch circuit or the feeder, and 5% for feeder and branch together. Informational notes are not enforceable requirements (NEC 90.5(C)), though a local amendment or a project specification can make a limit binding.
- How do you calculate three-phase voltage drop?
- Use √3 (1.732) in place of the 2: VD = 1.732 × K × L × I ÷ A, line to line. A 480 V three-phase feeder of 1/0 copper carrying 100 A for 200 ft drops 4.23 V (0.88%); the same run in aluminum drops 6.95 V (1.45%). In AC conductors of 2/0 and larger, skin effect makes the resistance higher than the DC value used here, so the real drop is somewhat larger; the page shows a note for those sizes instead of correcting K.
- What size wire do I need for 12 V at 20 amps?
- For a drop within 3% on copper: 10 AWG up to 5 ft one way, 8 AWG at 10 ft, 6 AWG at 15 ft and 4 AWG at 20 to 25 ft. At 15 ft, 10 AWG loses 0.75 V, 6.21% of 12 V. The wire’s current rating still has to be checked separately.
- Why does aluminum wire drop more voltage than copper?
- Aluminum has the higher resistance: K is 21.2 against 12.9 for copper, so the same size and run drops about 1.64 times as much. 12 AWG at 10 A for 100 ft on 120 V drops 6.49 V (5.41%) in aluminum and 3.95 V (3.29%) in copper.
Related Tools
View all toolsResistor Color Code Calculator
Read 4-, 5- and 6-band resistor color codes or SMD codes like 472 as ohms with tolerance, or type 4.7k to get its bands. Brown black red gold is 1 kΩ ±5%.
Ohm's Law Calculator
Enter any two of voltage (V), current (A), resistance (Ω) and power (W) to solve the other two with V = IR and P = VI, shown with SI prefixes.
LED Resistor Calculator
Series resistor for one LED or a string of LEDs from supply voltage, forward voltage and current: exact ohms, the E24 value above it, power and rating.
Battery Life Calculator
Battery runtime from mAh, mA and both voltages: 2,500 mAh at 3.7 V into a 500 mA, 5 V load through an 85% converter runs 3 h 9 min, not 5 h.
PCB Trace Width Calculator
PCB trace width from current, copper weight and temperature rise by the IPC-2221 formula, in mils and mm, plus the trace resistance and voltage drop.
Wire Gauge Ampacity Calculator
Pick a copper wire size from 14 AWG to 4/0 AWG for a load in amps and a run length, with the voltage drop. An orientation aid, not an NEC compliance check.