Skip to main content
CalcChef

Wire Gauge Ampacity Calculator

Pick a copper wire size from 14 AWG to 4/0 AWG for a load in amps and a run length, with the voltage drop. An orientation aid, not an NEC compliance check. How it works

Use the Wire Gauge Ampacity Calculator

Conductor size
12 AWG copper
Ampacity 25 A · Voltage drop 3.95 V (3.3%)
Size found, drop over limit: 12 AWG copper
Ampacity, 75 °C column
25 A
240.4(D) small-conductor limit
20 A
Voltage drop
3.95 V (3.3%)
Ambient correction
None (at or below 30 °C)

The drop is above 3%. 10 AWG copper keeps it within 3%.

Ampacity uses the NEC Table 310.16 75 °C copper column for every insulation type, which assumes equipment terminations marked for 75 °C (for equipment of 100 A or less NEC 110.14(C) uses the 60 °C column unless the equipment is marked 75 °C). Check the adopted NEC edition and the overcurrent device for the final design; this result does not show code compliance. Voltage drop is informational.

Scope: copper, 14 to 4/0 AWG, up to three current-carrying conductors, ambient at or below 30 °C. Larger sizes, aluminum, bundling and ambient correction are not covered.

About the Wire Gauge Ampacity Calculator

For a 20 A load on a 120 V single-phase circuit, 50 ft one way, this tool picks 12 AWG copper (25 A at 75 °C, 20 A under the 240.4(D) small-conductor limit) and warns that the voltage drop is 3.95 V, or 3.3%, over its 3% limit; 10 AWG brings it to 2.1%. It covers copper from 14 AWG to 4/0 AWG, where a 40 A load gets 8 AWG (50 A), and it is not an NEC compliance check.

The copper sizes this tool covers

SizeAreaAmpacity, 75 °C column240.4(D) limit
14 AWG4,110 CM20 A15 A
12 AWG6,530 CM25 A20 A
10 AWG10,380 CM35 A30 A
8 AWG16,510 CM50 ANone
6 AWG26,240 CM65 ANone
4 AWG41,740 CM85 ANone
3 AWG52,620 CM100 ANone
2 AWG66,360 CM115 ANone
1 AWG83,690 CM130 ANone
1/0 AWG105,600 CM150 ANone
2/0 AWG133,100 CM175 ANone
3/0 AWG167,800 CM200 ANone
4/0 AWG211,600 CM230 ANone

Ampacity is the 75 °C copper column of NEC Table 310.16 from Cerrowire’s chart, based on the 2017 NEC, which agrees with a study guide for 14 to 10 AWG; the 240.4(D) limits are from trade-press text and apply to 14, 12 and 10 AWG only. The code book itself was not read. Check both in the edition your area has adopted.

Size the tool picks by load current

Load currentSmallest size picked
10 A14 AWG copper
15 A14 AWG copper
16 A12 AWG copper
20 A12 AWG copper
21 A10 AWG copper
30 A10 AWG copper
31 A8 AWG copper
40 A8 AWG copper
50 A8 AWG copper
51 A6 AWG copper
66 A4 AWG copper
100 A3 AWG copper
150 A1/0 AWG copper
200 A3/0 AWG copper
230 A4/0 AWG copper
231 ANone of the covered sizes

For a 10 ft run at 240 V, single-phase. Voltage drop never changes the size the page picks, it only adds a warning. For 14, 12 and 10 AWG the 240.4(D) limit sets the size, because it is lower than the 75 °C ampacity; from 8 AWG up the ampacity does.

Voltage drop for 20 A at 120 V, single-phase, by one-way length

One-way length12 AWG10 AWG
25 ft1.98 V (1.6%)1.24 V (1.0%)
50 ft3.95 V (3.3%)2.49 V (2.1%)
75 ft5.93 V (4.9%)3.73 V (3.1%)
100 ft7.90 V (6.6%)4.97 V (4.1%)

VD = 2 × 12.9 × length × 20 / area in circular mils; the percent is of 120 V.

Methodology

A size qualifies when its 75 °C copper ampacity (14 AWG 20 A, 12 AWG 25 A, 10 AWG 35 A, 8 AWG 50 A, up to 4/0 AWG 230 A) and, for 14 to 10 AWG, its 240.4(D) limit (15, 20, 30 A) are both at least the load current. The smallest qualifying size is shown. Voltage drop = 2 × 12.9 × L × I / CM (single-phase) or √3 × 12.9 × L × I / CM (three-phase), as a percent of the system voltage.

Assumptions

  • Copper conductors, at most three current-carrying conductors and an ambient temperature of 30 °C or below.
  • All insulation types use the 75 °C ampacity column, so the insulation is not asked for.

How to use this tool

  1. Type the system voltage (12 to 480 V), the load current (0.1 to 1,000 A) and the one-way length, in ft or m.
  2. Choose single-phase or three-phase, and a voltage-drop limit of 1, 2, 3 or 5%. Keep the ambient temperature at 30 °C or below (−10 to 30 °C).
  3. Read the size, its ampacity and limit, and the voltage drop. If the drop is over your limit, the page names the smallest covered size that meets it.

Frequently asked questions

What size wire does this tool pick for 15, 20 and 30 amps?
14 AWG copper for loads up to 15 A, 12 AWG for 16 to 20 A and 10 AWG for 21 to 30 A, because the 240.4(D) limits are 15, 20 and 30 A. Above 30 A the 75 °C ampacity decides, and above 230 A no covered size qualifies and the page shows "No covered size". What is permitted on a real circuit is decided by the adopted NEC edition and your inspector.
Why does the page show 25 A for 12 AWG but a 20 A limit?
25 A is the 75 °C ampacity from Table 310.16; 20 A is the 240.4(D) limit on overcurrent protection for 12 AWG copper. The page requires both to reach the load, and for 14, 12 and 10 AWG the limit is lower, so it sets the size. The limits equal the 60 °C column, which is the column that applies to terminations on equipment rated 100 A or less unless the equipment is marked for 75 °C.
How is voltage drop calculated?
VD = 2 × K × L × I / CM for single-phase, with √3 in place of 2 for three-phase. K is 12.9 for copper, L the one-way length in ft, I the load in amps and CM the conductor area. On a 208 V three-phase circuit, 20 A over 50 ft on 12 AWG is √3 × 12.9 × 50 × 20 / 6530 = 3.42 V, or 1.6%, about half the 3.3% the same run loses at 120 V single-phase. The NEC’s 3% for a branch circuit is a recommendation in an informational note, not a requirement, and the limit here is informational.
What size wire for 40 amps?
8 AWG copper, whose 75 °C ampacity is 50 A; 10 AWG is out because its 240.4(D) limit is 30 A. Over 100 ft at 120 V that 8 AWG run drops 6.25 V, 5.2%, so with a 3% limit the page names 4 AWG (2.47 V, 2.1%). On 240 V over 50 ft the drop is 3.13 V, 1.3%. The ampacity assumes terminations marked for 75 °C; check the breaker and terminations with your inspector.
Does it correct for hot ambient temperatures or bundled conductors?
No. It refuses an ambient temperature above 30 °C with a message and assumes no more than three current-carrying conductors, so no correction factor is applied. At 30 °C or below the ambient correction is 1.00.

Related Tools

View all tools